SHORTCOMING(S)
With reference to your application ID 52026081305034 dated 23-09-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the M/s Priya Global at B-22, Mayapuri, Industrial Area, Phase-II,
New Delhi-64 from fire safety point of view in presence of Mr. Tarun, Owner on dated 21/08/2026 During the course
of inspection following observations were made:-
1. Smoke management system found removed in basement.
2. Fire Extinguisher found empty at some locations.
3. Hose reel hose and sprinkler system provided but found non functional.
4. Terrace level pump provided but found non functional.
5. Over head tank of capacity 10,000 liters provided against the requirement of 20,000 liters.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. PRIYA GLOBAL , EA191, TAGORE GARDEN, TAGORE GARDEN, DELHI, 110027
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026081305034 Dated: 23-09-2026
A.K.Malik
Chief Fire Officer
With reference to your application ID 52026081305034 dated 23-09-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the M/s Priya Global at B-22, Mayapuri, Industrial Area, Phase-II,
New Delhi-64 from fire safety point of view in presence of Mr. Tarun, Owner on dated 21/08/2026 During the course
of inspection following observations were made:-
1. Smoke management system found removed in basement.
2. Fire Extinguisher found empty at some locations.
3. Hose reel hose and sprinkler system provided but found non functional.
4. Terrace level pump provided but found non functional.
5. Over head tank of capacity 10,000 liters provided against the requirement of 20,000 liters.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. PRIYA GLOBAL , EA191, TAGORE GARDEN, TAGORE GARDEN, DELHI, 110027
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026081305034 Dated: 23-09-2026
A.K.Malik
Chief Fire Officer
Domain ID
DFS
Department of Delhi Fire Service