SHORTCOMING(S)
With reference to your application ID 52026061903802 dated 27-07-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Maharishi Dayanand Model Sec. School at 134, Arvind Enclave,
Nangloi, New Delhi-110041. from fire safety point of view in presence of Mrs. Nisha, Vice Principal on dated
14/07/2026 During the course of inspection following observations were made:-
1.First Aid hose reel found removed from the ground floor.
2.Terrace fire pumps were not found in auto mode during inspection.
3.4000 ltrs Over Head water captive tank provided against the required capacity of 5000 ltrs.
4.Exit signage’s found removed at some places.
5.One room was found constructed on the second-floor terrace
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Nisha Antil , 134 Arvind Enclave , Amar Colony, Nangloi, Delhi, 110041
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026061903802 Dated: 27-07-2026
Sachin Rana, IAS
Pr. Director
With reference to your application ID 52026061903802 dated 27-07-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Maharishi Dayanand Model Sec. School at 134, Arvind Enclave,
Nangloi, New Delhi-110041. from fire safety point of view in presence of Mrs. Nisha, Vice Principal on dated
14/07/2026 During the course of inspection following observations were made:-
1.First Aid hose reel found removed from the ground floor.
2.Terrace fire pumps were not found in auto mode during inspection.
3.4000 ltrs Over Head water captive tank provided against the required capacity of 5000 ltrs.
4.Exit signage’s found removed at some places.
5.One room was found constructed on the second-floor terrace
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Nisha Antil , 134 Arvind Enclave , Amar Colony, Nangloi, Delhi, 110041
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026061903802 Dated: 27-07-2026
Sachin Rana, IAS
Pr. Director
Domain ID
DFS
Department of Delhi Fire Service