SHORTCOMING(S)
With reference to your application ID 52026060503420 dated 03-08-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Industrial Building at Plot No. 34, Rajasthani Co-operative
Industrial Estate, G.T. Karnal Road, Delhi- 110033. from fire safety point of view in presence of Mr. Yash Bhardwaj
on dated 23/07/2026 During the course of inspection following observations were made:-
1. Mezzanine Floor has to be removed or regularized from the concerned building department.
2. Smoke ventilation system in basement found provided but not functional and also found removed at upper floor at
some places.
3. Detectors found removed at some places.
4. Sprinklers found removed at some places.
5. Standby DG pump found provided but not functional and pumping system not found in auto mode.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. ABHAY PRATAP SINGH , Plot No 34, Rajasthani cooperative, industrial estate ltd, Jahangirpuri, 110033
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026060503420 Dated: 03-08-2026
Sachin Rana, IAS
Pr. Director
With reference to your application ID 52026060503420 dated 03-08-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Industrial Building at Plot No. 34, Rajasthani Co-operative
Industrial Estate, G.T. Karnal Road, Delhi- 110033. from fire safety point of view in presence of Mr. Yash Bhardwaj
on dated 23/07/2026 During the course of inspection following observations were made:-
1. Mezzanine Floor has to be removed or regularized from the concerned building department.
2. Smoke ventilation system in basement found provided but not functional and also found removed at upper floor at
some places.
3. Detectors found removed at some places.
4. Sprinklers found removed at some places.
5. Standby DG pump found provided but not functional and pumping system not found in auto mode.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. ABHAY PRATAP SINGH , Plot No 34, Rajasthani cooperative, industrial estate ltd, Jahangirpuri, 110033
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026060503420 Dated: 03-08-2026
Sachin Rana, IAS
Pr. Director
Domain ID
DFS
Department of Delhi Fire Service