SHORTCOMING(S)
With reference to your application ID 52026031801696 dated 02-06-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Ideal Public School at Gali No. 2, B-Block, Swaroop Vihar, Delhi-
110034 from fire safety point of view in presence of Ms. Karnika, Principal on dated 25/05/2026 During the course of
inspection following observations were made:-
1. Hose Reel Hose is provided but found non-functional and damaged condition.
2. Terrace level fire pump capacity of 220 LPM is provided but found non-functional and damaged condition.
3. Terrace level water tank of capacity 2500 ltrs. is being used for domestic purpose. Fire water tank must be
dedicated to firefighting purpose only.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. URMILA RANI , A-15282, A-BLOCK, GALI NO.-17, BURARI, DELHI, 110084
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026031801696 Dated: 02-06-2026
S.K.DUA
Chief Fire Officer
With reference to your application ID 52026031801696 dated 02-06-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Ideal Public School at Gali No. 2, B-Block, Swaroop Vihar, Delhi-
110034 from fire safety point of view in presence of Ms. Karnika, Principal on dated 25/05/2026 During the course of
inspection following observations were made:-
1. Hose Reel Hose is provided but found non-functional and damaged condition.
2. Terrace level fire pump capacity of 220 LPM is provided but found non-functional and damaged condition.
3. Terrace level water tank of capacity 2500 ltrs. is being used for domestic purpose. Fire water tank must be
dedicated to firefighting purpose only.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. URMILA RANI , A-15282, A-BLOCK, GALI NO.-17, BURARI, DELHI, 110084
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.