SHORTCOMING(S)
With reference to your application ID 52026030901484 dated 07-04-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Guru Tegh Bahadur Public School at Gurudwara Siri Guru
Singh Sabha, Lajpat Nagar - I, Krishna Market, New Delhi - 110024 from fire safety point of view in presence of Mr.
Ravinder Singh on dated 24/03/2026 During the course of inspection following observations were made:-
1.Fire extinguisher provided but found empty.
2.First-Aid-Hose Reel at each floor provided but not functional.
3.Terrace level fire pump provided but not functional.
4.Overhead tank of 5000 liters capacity is provided against the requirement of 10,000 liters.
5.Exit & floors Signage's not provided in strategic location in the building.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Ravinder Singh , 93, BLOCK E,, LAJPAT NAGAR 1,, DEFENCE COLONY, DELHI, 110024
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026030901484 Dated: 07-04-2026
A.K.Malik
Dy.Chief Fire Officer
With reference to your application ID 52026030901484 dated 07-04-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Guru Tegh Bahadur Public School at Gurudwara Siri Guru
Singh Sabha, Lajpat Nagar - I, Krishna Market, New Delhi - 110024 from fire safety point of view in presence of Mr.
Ravinder Singh on dated 24/03/2026 During the course of inspection following observations were made:-
1.Fire extinguisher provided but found empty.
2.First-Aid-Hose Reel at each floor provided but not functional.
3.Terrace level fire pump provided but not functional.
4.Overhead tank of 5000 liters capacity is provided against the requirement of 10,000 liters.
5.Exit & floors Signage's not provided in strategic location in the building.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Ravinder Singh , 93, BLOCK E,, LAJPAT NAGAR 1,, DEFENCE COLONY, DELHI, 110024
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026030901484 Dated: 07-04-2026
A.K.Malik
Dy.Chief Fire Officer
Domain ID
DFS
Department of Delhi Fire Service