SHORTCOMING(S)
With reference to your application ID 52026020400823 dated 06-03-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Rising Star Junior School at Sector-10, Dwarka, New Delhi-
110075 from fire safety point of view in presence of Ms. Monika on dated 23/02/2026 During the course of inspection
following observations were made:-
1. First aid hose reel found non-functional
2. Terrace level fire pumps not found automatic in operation.
3. Overhead water storage exclusively for firefighting found used for domestic purposes.
4. Basement floor is used for school activities. Class room found constructed and alternate staircase is accessible
through class room.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Rising Stars Junior School , RisingStarsJuniorSchool, Sector-10, Dwarka, New Delhi, 110075
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026020400823 Dated: 06-03-2026
A.K.Malik
Dy.Chief Fire Officer
With reference to your application ID 52026020400823 dated 06-03-2026 on the subject cited above, it is informed that
officer concerned of this department inspected the Rising Star Junior School at Sector-10, Dwarka, New Delhi-
110075 from fire safety point of view in presence of Ms. Monika on dated 23/02/2026 During the course of inspection
following observations were made:-
1. First aid hose reel found non-functional
2. Terrace level fire pumps not found automatic in operation.
3. Overhead water storage exclusively for firefighting found used for domestic purposes.
4. Basement floor is used for school activities. Class room found constructed and alternate staircase is accessible
through class room.
In view of the above, the building can not be considered for issuance of Fire Safety Certificate at this stage. Therefore,
the application is rejected with the directions to apply again after compliance of above mentioned shortcomings under
intimation to this office for further course of action.
Copy to:-
1. Rising Stars Junior School , RisingStarsJuniorSchool, Sector-10, Dwarka, New Delhi, 110075
2. The Concerned Local/Statutory Authority –
This letter is computer generated and does not require signature.
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE: NEW DELHI – 110001
Application ID. 52026020400823 Dated: 06-03-2026
A.K.Malik
Dy.Chief Fire Officer
Domain ID
DFS
Department of Delhi Fire Service