The building plans shall be prepared as per bye-law 2.6 UBBL 2016 and must contain the information mentioned under bye-law 2.7 & 2.8.

The design and installation of the Automatic Sprinkler System shall be as per the specifications contained in IS 15105 published by Bureau of Indian Standards. Sprinkler design plans and calculation shall be provided along-with building plans.

The smoke management systems shall be fully ducted and air changes requirement shall be as per National Building Code of India/ International codes. The fresh air supply shall be discharged at ground level and the exhaust shall be taken out from ceiling level. Smoke management plans and calculation shall be provided along-with building plans.

If the height of the proposed building is more than 15 meters than model of the building is required. The 3 D model of same can be provided online.

Yes, but only for the buildings covered under rule 27 of Delhi Fire Service Rules 2010 and Bye–Law 2.8 of UBBL 2016. The fire safety guidelines/ recommendations clearly specify as to what type of fire and life safety systems are to be installed in the building.

For buildings more than 24 meters in height, the refuge area as per bye-law 9.3.6 of UBBL-2016  is required to be provided.

The list is as under;

  1. Residential buildings (other than hotels and guest houses) having height more than 15 meters or having ground plus four upper stories including mezzanine floor.
  2. Hotels and guest houses having height more than 12 meters having ground plus three upper stories including mezzanine floor.

(3) Educational buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.

(4) Institutional buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.

(5) All Assembly buildings.

(6) Business buildings having height more than 15 meters or having ground plus four upper stories including mezzanine floor.

(7)  Mercantile buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.

(8) Industrial buildings having covered area on all floors more than 250 square meters.

(9) Storage buildings having covered area on all floors more than 250 square meters.

(10) All Hazardous buildings having covered area on all floors more than 100 square meters. 

(11) Underground Structures.

Helipad is required to be provided on the terrace of those buildings which have height more than 200 meters as per bye-law 8.6 of UBBL-2016.